Improvement of manifold design in heat exchangers: pressure drop and flow analysis using cfd and experimental methods

  1. Tez No: 1031433
  2. Yazar: YASİN NEHİR
  3. Danışmanlar: DOÇ. DR. NEHİR TOKGÖZ
  4. Tez Türü: Yüksek Lisans
  5. Konular: Enerji, Makine Mühendisliği, Energy, Mechanical Engineering
  6. Anahtar Kelimeler: Akışkanlar mekaniği, Analiz yöntemleri, Bilgisayar destekli tasarım, Eşanjörler, Hesaplamalı akışkanlar dinamiği (HAD), Fluid mechanics, Analysis methods, Computer aided design, Computational fluid dynamics (HAD)
  7. Yıl: 2026
  8. Dil: Türkçe
  9. Üniversite: Sakarya Üniversitesi
  10. Enstitü: Fen Bilimleri Enstitüsü
  11. Ana Bilim Dalı: Makine Mühendisliği Ana Bilim Dalı
  12. Bilim Dalı: Enerji Bilim Dalı
  13. Sayfa Sayısı: Belirtilmemiş.

Özet

Bu tez çalışması, bir ısı eşanjörü–kolektör sisteminde gözlemlenen yüksek basınç düşümünün nedenlerini belirlemek, akış karakteristiğini bütüncül Şekilde incelemek ve kolektör geometrisini optimize ederek sistemin hidrolik performansını iyileştirmek amacıyla gerçekleştirilmiştir. Isı eşanjörleri modern enerji sistemlerinde, iklimlendirme uygulamalarında ve endüstriyel proseslerde kritik bir bileşen olup, bu cihazların basınç kayıplarının azaltılması hem enerji verimliliğini hem de işletme maliyetlerini doğrudan etkilemektedir. Bu sebeple çalışma, hidrolik tasarıma yönelik mühendislik iyileştirmeleri ve sayısal model doğrulama açısından katkı sunmaktadır. Araştırma, deneysel ölçümler ile sayısal analizleri birleştiren hibrit bir metodolojiyle yürütülmüştür. İlk aşamada, ısı eşanjörü ve kolektörün oluşturduğu sistem prototip üzerinde test edilerek farklı kütlesel debilerde toplam basınç düşüşü (ΔP) değerleri yüksek hassasiyetli diferansiyel basınç sensörleri ile ölçülmüştür. Deneysel çalışma 0.0649–0.106 kg/s aralığında toplam 10 farklı debide su ile yapılmıştır. Akışkanının yoğunluk–viskozite gibi termofiziksel özellikleri deney süresince sabit kabul edilmiştir. Deneysel veriler, hem sistemin gerçek hidrolik davranışını ortaya koymuş hem de HAD modelin doğrulanması için kullanılmıştır. Sayısal modelleme aşaması, ANSYS Fluent yazılımı kullanılarak üç boyutlu akış alanının oluşturulmasıyla gerçekleştirilmiştir. CAD geometrisi, test edilen fiziksel sistem ile birebir aynı olacak Şekilde modellenmiş; polyhedral mesh yapısı oluşturulmuştur. Türbülans modellemesi için endüstride yaygın kullanımı, kararlılığı ve yüksek Reynolds sayılı iç akışlarda sağladığı doğruluk nedeniyle Standard k–ε türbülans modeli seçilmiştir. Model doğrulama sürecinde, HAD sonuçları deneysel ölçümlerle karşılaştırılarak değerlendirilmiştir. Elde edilen basınç düşümü değerleri incelendiğinde, sayısal modelin deneysel verileri tüm debi aralığında başarılı Şekilde temsil ettiği görülmüştür. Özellikle Tablo 3.1'de görülebileceği gibi en yüksek sapmanın olduğu kütlesel debide ΔP_test = 16,2 kPa ve ΔP_HAD = 13,93 kPa değerleri arasındaki farkın %16,3 değerinde gerçekleşmesi en düşük sapmanın olduğu kütlesel debide ise ΔP_test = 9,8 kPa ve ΔP_HAD = 9,81 kPa değerlerin arasındaki farkın %0,1 değerinde olması, hem literatürde kabul edilen hata sınırları içinde yer almakta hem de HAD modelinin optimizasyon çalışmaları için güvenilir bir araç olduğunu kanıtlamaktadır. Tüm debi aralığına bakıldığında deneysel ve sayısal sonuçlar arasındaki ortalama uyumsuzluk yalnızca %7,3 olarak bulunmuştur. HAD ve deneysel basınç düşümü değerleri arasındaki ortalama farkın %7,3 olması, literatürde benzer çalışmalar için rapor edilen hata seviyeleriyle uyumludur. Örneğin helezonik borulu bir ısı eşanjör çalışmasında HAD ve deneysel basınç düşümü sonuçları arasında yaklaşık %9,5'lik relatif hata bulmuş ve bu farkı“iyi uyum”olarak değerlendirmiştir [1] Tezin ikinci aşaması, kolektör giriş konumunun (A = 20 mm, 40 mm, 60 mm, 80 mm, 110 mm, 140 mm) sistem üzerindeki etkisinin detaylı olarak incelendiği optimizasyon bölümüdür. Her bir konum için üç farklı kütlesel debide hız dağılımı, statik basınç konturları ve çıkışlardaki debi oranları analiz edilmiştir. Elde edilen bulgular, akışın kolektör içerisindeki davranışının giriş konumuna son derece duyarlı olduğunu göstermektedir. A = 20 mm konumunda dirsek çevresinde güçlü yerel hızlanmalar, geniş vorteks bölgeleri ve çıkışlar arasında belirgin debi dengesizliği gözlenmiş; bu durum toplam basınç kaybının artmasına neden olmuştur. Orijinal konum olan A = 40 mm'de bu dengesizlik bir miktar azalmış olsa da akış hâlâ tamamen homojen değildir. A = 60 mm konumu ise tüm analizlerde en iyi performansı göstermiştir. Bu konumda akış çıkışlara neredeyse eşit oranlarda dağılmış, hız profilleri dengeli seyretmiş ve yerel kayıplar minimum düzeye inmiştir. Tüm debi aralığında basınç kayıpları diğer konumlara göre daha düşük çıkmış; özellikle çıkışlar arasındaki debi oranlarının birbirine çok yakın olması, akış homojenliğinin sağlandığını göstermiştir. Bu nedenle A=60 mm konumu hidrolik açıdan optimum kolektör geometrisi olarak belirlenmiştir. A=80 mm, 110 mm ve 140 mm konumlarında da genel olarak dengeli hız dağılımları elde edilmiş olsa da hem ΔP değerleri hem de debi dağılımı açısından 60 mm konumu kadar iyi bir performans sağlanamamıştır. Özellikle A=140 mm gibi daha uzak konumlarda akış alt çıkışlara yönelme eğilimi göstermiş ve düşey akışın oluşturduğu hidrolik direnç bazı bölgelerde artmıştır. Farklı brench boru sayısına sahip kolektör analizleri sonucunda ise brench boru sayısının basıncı düşürdüğü ve akış dağılımına katkı sağladığı gözlemlenmiştir. Kolektörun silindirik kısmı uzunluğunun da analizleri yapılarak hız dagılımı ve basınç kaybı açısından değerlendirilmiştir. Yapılan analizler sonucunda, branş borusu sayısı ile kolektörün silindirik bölümünün uzunluğunun akış dağılımı ve basınç kaybı üzerindeki etkileri ortaya koymuştur. Kolektörün silindirik kısım çapı da çalışma kapsamında değerlendirilmiş, çap değişiminin hem çıkışlar arasındaki hız dağılımı hem de toplam basınç düşümü üzerindeki etkisinin diğer değişkenlere kıyasla daha sınırlı kaldığı tespit edilmiştir. Bu durum, silindir kısımdaki çap büyütme veya küçültmenin akış karakteristiklerini ikincil düzeyde değiştirdiğini buna karşın kolektör uzunluğu ve çıkış sayısı gibi parametrelerin akış özellikleri bakımından ve basınç gradyanı açısından çok daha belirleyici olduğunu göstermektedir. Bu bulgular sonucunda, kolektör geometrisinin ısı eşanjörü performansı üzerindeki belirleyici rolü açık şekilde ortaya koyulmuştur. Doğrulanmış HAD modeli sayesinde deneysel doğrulama maliyetlerinin düşürülmesi, tasarım değişikliklerinin hızlı bir şekilde değerlendirilebilmesi ve ısı eşanjörü tasarımlarında simülasyon odaklı geliştirme süreçlerinin uygulanabilir hâle gelmesi bu tezin önemli mühendislik çıktıları arasındadır. Sonuç olarak bu çalışma, kolektör geometrisinin optimize edilmesinin ısı eşanjörlerinde basınç kaybını düşürmek için kritik bir strateji olduğunu ortaya koymuş; deneysel ve sayısal yöntemlerin birlikte kullanımının güvenilir ve etkili bir mühendislik yaklaşımı sunduğunu göstermiştir. Elde edilen sonuçlar hem mevcut sistemin performansını iyileştirmekte hem de benzer ısı eşanjörü tasarımları için bilimsel ve uygulamalı bir referans oluşturmaktadır.

Özet (Çeviri)

This thesis was conducted to determine the causes of the high pressure drop observed in a heat exchanger–manifold system, to comprehensively investigate its flow characteristics, and to improve the hydraulic performance of the system by optimizing the manifold geometry. Heat exchangers are critical components in modern energy systems, HVAC applications, and industrial processes, and reducing pressure losses in these devices directly affects both energy efficiency and operating costs. Therefore, this study contributes to engineering improvements in hydraulic design and the validation of numerical models. The research was carried out using a hybrid methodology combining experimental measurements and numerical analyses. In the first stage, the heat exchanger–manifold system was tested on a prototype, and total pressure drop (ΔP) values at different mass flow rates were measured using high-precision differential pressure sensors. The experimental study was performed with water at a total of ten different flow rates ranging from 0.0649 to 0.106 kg/s. The thermophysical properties of the working fluid, such as density and viscosity, were assumed to remain constant throughout the experiments. The experimental data not only revealed the actual hydraulic behavior of the system but also served as a basis for validating the CFD model. The numerical modeling phase was conducted using ANSYS Fluent by generating a three-dimensional flow domain. The CAD geometry was modeled to be identical to the tested physical system, and a polyhedral mesh structure was created. The Standard k–ε turbulence model was selected because of its widespread industrial use, numerical stability, and proven accuracy for high-Reynolds-number internal flow applications. Simulations were performed under steady-state flow conditions. A mass flow inlet boundary condition was prescribed at the inlet, while the outlet boundary condition was defined as a gauge pressure of 0 Pa. During the model validation process, CFD results were evaluated through comparison with experimental measurements. The pressure drop values demonstrated that the numerical model successfully represented the experimental data across the entire flow-rate range. As shown in Table 3.1, at the mass flow rate corresponding to the highest deviation, the difference between ΔP_test = 16.2 kPa and ΔP_CFD = 13.93 kPa was 16.3%, whereas at the mass flow rate corresponding to the lowest deviation, the difference between ΔP_test = 9.8 kPa and ΔP_CFD = 9.81 kPa was only 0.1%. These deviations fall within the acceptable error limits reported in the literature and demonstrate that the CFD model is a reliable tool for optimization studies. Considering the entire flow-rate range, the average discrepancy between experimental and numerical results was found to be only 7.3%. This average difference is consistent with error levels reported in similar studies in the literature. For example, a study on a helical-coil heat exchanger reported an approximately 9.5% relative error between CFD and experimental pressure-drop results and described this level of deviation as“good agreement”[1]. The second stage of the thesis focused on optimization, where the effects of manifold inlet position (A = 20 mm, 40 mm, 60 mm, 80 mm, 110 mm, and 140 mm) on system performance were investigated in detail. For each inlet position, velocity distributions, static pressure contours, and outlet flow-rate ratios were analyzed at three different mass flow rates. The findings revealed that the flow behavior inside the manifold is highly sensitive to the inlet location. At A = 20 mm, strong local accelerations around the elbow region, extensive vortex zones, and significant flow-rate imbalances among the outlets were observed, resulting in increased total pressure loss. Although these imbalances were reduced to some extent at the original position of A = 40 mm, the flow distribution was still not completely uniform. Among all configurations, the A = 60 mm inlet position exhibited the best overall performance. At this location, the flow was distributed almost equally among the outlets, velocity profiles remained well balanced, and local losses were minimized. Pressure losses were lower than those of the other configurations throughout the entire flow-rate range. Furthermore, the similarity of the outlet flow-rate ratios indicated a high degree of flow uniformity. Therefore, the A = 60 mm configuration was identified as the hydraulically optimal manifold geometry. Although generally balanced velocity distributions were also achieved at A = 80 mm, 110 mm, and 140 mm, none of these configurations matched the performance of the 60 mm position in terms of pressure drop and flow distribution. In particular, at the more distant inlet location of A = 140 mm, the flow tended to migrate toward the lower outlets, and the hydraulic resistance associated with the vertical flow path increased in certain regions. Additional analyses were performed to investigate manifolds with different numbers of branch tubes. The results showed that increasing the number of branch tubes reduced pressure losses and contributed positively to flow distribution. The influence of the cylindrical section length of the manifold was also examined and evaluated in terms of velocity distribution and pressure loss. The analyses demonstrated the significant effects of both branch tube number and cylindrical section length on flow distribution and pressure drop characteristics. The diameter of the manifold's cylindrical section was also assessed within the scope of the study. It was found that variations in diameter had a more limited effect on both the outlet velocity distribution and the total pressure drop compared to the other design parameters. This finding indicates that increasing or decreasing the diameter of the cylindrical section modifies the flow characteristics only to a secondary degree. In contrast, parameters such as manifold length and the number of outlet branches have a much more pronounced influence on flow behavior and pressure gradients. Overall, the results clearly demonstrate the critical role of manifold geometry in determining heat exchanger performance. Through the validated CFD model, the reduction of experimental validation costs, rapid evaluation of design modifications, and implementation of simulation-driven development processes in heat exchanger design emerged as important engineering outcomes of this study. In conclusion, this research has shown that optimization of manifold geometry is a critical strategy for reducing pressure losses in heat exchangers. Furthermore, the combined use of experimental and numerical methods has been demonstrated to provide a reliable and effective engineering approach. The results not only improve the performance of the existing system but also establish a scientific and practical reference for the design of similar heat exchanger systems. Furthermore, the reduced pressure losses achieved through the optimization of the manifold geometry have the potential to decrease the pumping power required by the system. A reduction in pressure drop directly contributes to lowering the pump head needed to circulate the working fluid throughout the system. Consequently, pumps with lower power requirements can be selected under the same operating conditions, leading to a reduction in the overall energy consumption of the system. Particularly in industrial applications that operate continuously over extended periods, even modest improvements in pumping power requirements can result in significant savings in operating costs. In addition, systems with lower pressure losses allow the consideration of lower-capacity pump alternatives during the pump selection process, thereby contributing to a reduction in initial investment costs. Operating the pump under reduced hydraulic loading also minimizes mechanical stresses on the equipment, which can help decrease maintenance requirements and reduce the risk of failures during service life. As a result, economic benefits can be achieved not only through lower energy consumption but also through reduced maintenance costs and extended equipment lifespan. In this context, the manifold optimization studies carried out within the scope of this research have demonstrated significant benefits not only in terms of improving flow distribution and reducing pressure losses, but also in lowering the overall life-cycle costs of the system. The findings indicate that future heat exchanger designs can benefit from the simultaneous consideration of hydraulic performance and economic criteria, providing valuable guidance for the development of more efficient, sustainable, and cost-effective systems.

Benzer Tezler

  1. Delikli plakalardaki akış karakteristiği ve basınç kaybının nümerik ve deneysel olarak incelenmesi

    Numerical and experimental investigation of flow characteristics and pressure loss in perforated plates

    MUHAMMED FURKAN BÜYÜKYILDIZ

    Yüksek Lisans

    Türkçe

    Türkçe

    2025

    Yıldız Teknik Üniversitesi

    Makine Mühendisliği Ana Bilim Dalı

    Yükleniyor...

  2. Eksenel kompresörlerde oluk genişliği ve en-boy oranının aerodinamik performansa etkisinin HAD ile analizi

    CFD-based analysis of casing groove width and aspect ratio effects on axial compressor aerodynamic performance

    KEREM ÖZÇELİK

    Yüksek Lisans

    Türkçe

    Türkçe

    2025

    İstanbul Teknik Üniversitesi

    Makine Mühendisliği Ana Bilim Dalı

    Yükleniyor...

  3. Buzdolabına adapte edilebilen, katmanlı donma yöntemi ile saydam buz yapabilen bir buz makinası konstrüksiyonu

    A refrigerator adaptable ice machine design that can make clear ice using fractional freezing method

    ÇETİN USLU

    Yüksek Lisans

    Türkçe

    Türkçe

    2015

    İstanbul Teknik Üniversitesi

    Makine Mühendisliği Ana Bilim Dalı

    Yükleniyor...

  4. Evaluation of an automotive air intake system in terms of pressure loss and flow characteristics

    Bir araç hava emiş sisteminin basınç kayıpları ve akış karakteristikleri açısından incelenmesi

    ANIL CAN AĞAR

    Yüksek Lisans

    İngilizce

    İngilizce

    2015

    İstanbul Teknik Üniversitesi

    Makine Mühendisliği Ana Bilim Dalı

    Yükleniyor...

  5. Francis turbine design and optimization by using CFD

    HAD analizleri yardımı ile francis türbin tasarımı ve optimizasyonu

    BERK CAN DUVA

    Yüksek Lisans

    İngilizce

    İngilizce

    2016

    İstanbul Teknik Üniversitesi

    Enerji Bilimi ve Teknolojileri Ana Bilim Dalı

    Yükleniyor...