Bir tıp fakültesi hastanesi iç ortam hava kalitesi ve ortamda bulunanlara etkisi

A faculty of medicine hospital indoor air quality and its effect on those in the environment

  1. Tez No: 674369
  2. Yazar: GÜLLÜ EREN
  3. Danışmanlar: DOÇ. DR. LÜTFİ SALTUK DEMİR
  4. Tez Türü: Tıpta Uzmanlık
  5. Konular: Halk Sağlığı, Public Health
  6. Anahtar Kelimeler: Belirtilmemiş.
  7. Yıl: 2021
  8. Dil: Türkçe
  9. Üniversite: Necmettin Erbakan Üniversitesi
  10. Enstitü: Meram Tıp Fakültesi
  11. Ana Bilim Dalı: Halk Sağlığı Ana Bilim Dalı
  12. Bilim Dalı: Belirtilmemiş.
  13. Sayfa Sayısı: 126

Özet

Amaç: Bu çalışmada Necmettin Erbakan Üniversitesi Meram Tıp Fakültesi Hastanesi'nde iç ortam hava kalitesi parametrelerini ölçmek ve hastane çalışanları ile hasta/hasta yakınlarının iç ortamla ilgili sağlık yakınmalarını tespit etmek amaçlanmıştır. Yöntem: Necmettin Erbakan Üniversitesi Meram Tıp Fakültesi Hastanesi'nde 28 Şubat – 22 Mart 2021 tarihleri arasında yapılan kesitsel tipteki bu araştırmada, 442 katılımcıya, yüz yüze görüşme yöntemiyle anket uygulanmıştır. Hastane iç ortam hava kalitesi için sıcaklık, bağıl nem, hava akım hızı, aydınlık düzeyi, NO, H 2 S, SO 2 , CO, CO 2 gaz ölçümleri yapılarak ölçüm sonuçları standartlara göre değerlendirilmiştir. Verilerin analizleri bilgisayar ortamında IBM SPSS 27.0 programında yapılmıştır. Bulgular: Çalışmada ölçülen hava sıcaklığı ortalaması 22,81±2,03 °C olarak tespit edildi. Ölçümlerin %80,3'ünün standartlara uygun olduğu belirlendi. Çalışmadaki bağıl nem ölçümlerinin ortancası %20,85 (16,62-29,00) ve tüm ölçümlerin % 22,7'si standartlara uygundu. Ölçümlerin neredeyse tümünde hava akımı hızının standartlara uygun olmadığı belirlendi. Aydınlatma düzeyi ölçümlerinin %81,0'ının standartlara uygun olmadığı belirlendi. İç ortam partiküler madde düzeyi ölçümü ile tüm ortamların ISO 5 sınıfına ait olduğu tespit edildi. İç ortam gaz ölçümleri sonucu hastanede NO, H 2 S, SO 2 gazlarına rastlanmadı. CO gazı hastanenin küçük bir kısmında tespit edildi. CO 2 ölçümlerinin neredeyse tamamı standartlara uygundu. Katılımcıların %53,2'si kadın, %46,8'i erkekti. Katılımcıların hastane iç ortamı ile ilgili en sık görülen yakınmaları yorgunluk, ortam havasından bunalma, uyku hali olarak tespit edildi. Sonuç: İç ortam hava kalitesi parametrelerinden bir kısmının standartlara uymadığı ve buna bağlı katılımcıların sağlık yakınmaları belirlenmiştir. İç ortam hava kalitesi parametreleri düzenli aralıklarla ölçülmeli ve standartlara uygun olması için gerekli düzenlemeler yapılmalıdır.

Özet (Çeviri)

Objective: In this study, it was aimed to measure indoor air quality parameters in Necmettin Erbakan University Meram Medical Faculty Hospital and to determine the health complaints of hospital staff and patients/patient relatives related to the indoor environment. Method: In this cross-sectional study conducted in Necmettin Erbakan University Meram Medical Faculty Hospital between February 28 - March 22, 2021, a questionnaire was applied to 442 participants by face-to-face interview method. For the indoor air quality of the hospital, temperature, relative humidity, air flow rate, illumination level, NO, H 2 S, SO 2 , CO, CO 2 gas measurements were made and the measurement results were evaluated according to the standards. Analysis of the data was made in computer environment using IBM SPSS 27.0 program. Results: The average air temperature measured in the study was found to be 22.81 ± 2.03 °C. It was determined that 80.3% of the measurements were in accordance with the standards. The median of the humidity measurements in the study was 20.85% (16.62- 29.00) and 22.7% of all measurements were in compliance with the standards. In almost all of the measurements, it was determined that the air flow velocity did not comply with the standards. It was determined that 81.0% of the lighting level measurements did not comply with the standards. With the indoor particulate matter level measurement, it was seen that all environments belong to ISO 5 class. NO, H 2 S, SO 2 gases were not found in the hospital as a result of indoor gas measurements. CO gas was detected in a small part of the hospital. Almost all of the CO 2 measurements were in compliance with the standards. Of all the participants, 53.2% were women and 46.8% were men. The most common complaints of the participants about the internal environment of the hospital were determined as fatigue, exhaustion from the ambient air, and sleepiness. Conclusion: Some of the indoor air quality parameters did not comply with the standards and the health complaints of the participants were determined. Indoor air quality parameters should be measured at regular intervals and necessary arrangements should be made to bring them into compliance with the standards.

Benzer Tezler

  1. ''Tek havayolu tek hastalık ''teorisi doğru mu?

    Is the theory ''one airway one disease'' true?

    DİDEM TUNALI

    Tıpta Uzmanlık

    Türkçe

    Türkçe

    2006

    Allerji ve İmmünolojiCelal Bayar Üniversitesi

    DOÇ.DR. CENGİZ KIRMAZ

  2. Obstrüktif uyku apne sendromlu hastalarda pozitif basınç tedavisinin böbrek fonksiyonları, kan basıncı ve endotel disfonksiyonu üzerine etkisi

    Effect of positive pressure therapy on endothelial dysfunction, blood pressure and renal fuctions in patients with obstructive sleep apnea syndrome

    ALPER KOÇ

    Tıpta Uzmanlık

    Türkçe

    Türkçe

    2015

    NefrolojiDüzce Üniversitesi

    İç Hastalıkları Ana Bilim Dalı

    DOÇ. DR. TANSU SAV

  3. Alt solunum yolu enfeksiyonu tanısı alan çocuklarda D vitamini düzeyi

    Vitamin D level in children diagnosed with lower respiratory track infection

    ABDULLAH ÖCAL YAĞINÇ

    Tıpta Uzmanlık

    Türkçe

    Türkçe

    2022

    Çocuk Sağlığı ve HastalıklarıÇukurova Üniversitesi

    Çocuk Sağlığı ve Hastalıkları Ana Bilim Dalı

    DOÇ. DR. DERYA ALABAZ

  4. Dokuz Eylül Üniversitesi Hastanesi yenidoğan yoğun bakım ünitesinde 2014-2018 yılları arasında izlenen çok düşük doğum ağırlıklı bebeklerde mortalite ve morbidite sonuçları ve önceki sonuçlarla karşılaştırılması

    Assessment and comparison of the mortality and morbidityrates of very low birth weight (VLBW) infants followedbetween years 2014-2018 in Dokuz Eylül University Faculty ofmedicine neonatal intensive care unit with previous results

    YAĞMUR DAMLA AKÇURA

    Tıpta Uzmanlık

    Türkçe

    Türkçe

    2019

    Çocuk Sağlığı ve HastalıklarıDokuz Eylül Üniversitesi

    Çocuk Sağlığı ve Hastalıkları Ana Bilim Dalı

    PROF. DR. NURAY DUMAN

  5. Bağışıklık yetmezliği olan hastalarda aspergilloz ve diğer fırsatçı küf enfeksiyonlarının araştırılması ve küf mantarlarının hastane çevresi ile hastane enfeksiyonu açısından önemi

    Investigation of aspergillosis and other opportunistic mold infections in immunocompromised patients and the importance of molds in nosocomial infections and presence of molds' in hospital environment

    AYŞE EREN

    Tıpta Uzmanlık

    Türkçe

    Türkçe

    2004

    MikrobiyolojiGazi Üniversitesi

    Tıbbi Mikrobiyoloji Ana Bilim Dalı

    PROF.DR. SEMRA KUŞTİMUR