Nanokristal nüveli orta frekanslı güç transformatörlerinde harmonik kaynaklı titreşimlerin incelenmesi
Investigation of vibration effects caused by harmonics medium frequency nanocrystalline core power transformers
- Tez No: 545641
- Danışmanlar: PROF. DR. İBRAHİM SEFA
- Tez Türü: Doktora
- Konular: Elektrik ve Elektronik Mühendisliği, Electrical and Electronics Engineering
- Anahtar Kelimeler: Güç transformatörü, Mekanik titreşim, Power transformer, Mechanical vibration
- Yıl: 2019
- Dil: Türkçe
- Üniversite: Gazi Üniversitesi
- Enstitü: Fen Bilimleri Enstitüsü
- Ana Bilim Dalı: Elektrik-Elektronik Mühendisliği Ana Bilim Dalı
- Bilim Dalı: Belirtilmemiş.
- Sayfa Sayısı: Belirtilmemiş.
Özet
Bu çalışmada nanokristal ve %6,5 SiFe nüve malzemelerinin kullanıldığı aynı güç değerindeki iki orta frekans transformatörünün titreşimleri incelenmiştir. İlk olarak sinüzoidal ve kare dalga uyarım şekillerinde 50Hz, 400Hz ve 10kHz çalışma frekanslarında elektromanyetik analizler yapılmıştır. Bu analizlerde boş çalışma ile nüve malzemesinin titreşimi belirlenmiş daha sonra farklı yüklenme seviyelerinin bu titreşimlerin üzerindeki etkileri belirlenmiştir. Elektromanyetik analizlerde her bir çalışma durumu için nüve akı yoğunluğu ile nüve kuvvet dağılımları belirlenmiştir. Daha sonra titreşim ivmelerinin belirlenmesi için harmonik tepki analizleri yapılmıştır. Nanokristal nüvenin orta frekansta çalışması sonucunda ortaya çıkan ivme harmonik bileşenlerinin %6,5 SiFe nüveye göre daha küçük olduğu görülmüştür. Yüklenme seviyesinin artması nanokristal nüvenin ivme harmonik genliklerinde daha büyük artışa yol açsa da %6,5 SiFe nüvenin ivme harmonik genlikleri daha yüksek kalmıştır. Her iki nüve için sinüzoidal uyarımda elde edilen ivme harmonik genliklerinin kare dalga uyarıma göre daha düşük değerlerde olduğu görülmüştür. 50Hz çalışma altında elde edilen ivme harmonik spektrumunun orta frekans ivme harmonik spektrumuna göre çok daha düzgün olduğu görülmüştür.
Özet (Çeviri)
In this study the vibrations of two medium frequency transformers with the same power value using nanocrystalline and 6.5% SiFe core materials were investigated. First, electromagnetic analyzes were performed at 50Hz, 400Hz and 10kHz operating frequencies under sinusoidal and square wave excitation modes. In these analyzes, the vibration of the core material was determined under the no-load operation, and then the effects of different loading levels on these vibrations were determined. In electromagnetic analyzes, core flux density and core force distributions were determined for each operating case. Then, harmonic response analyzes were performed to determine the vibration acceleration. The acceleration harmonic components of the nanocrystalline core were found to be smaller than 6.5% SiFe core under medium frequency operation. Although the increase in the loading level led to a greater increase in the acceleration harmonic amplitudes of the nanocrystalline core, the acceleration harmonic amplitudes of the 6.5% SiFe core remained higher. The acceleration harmonic amplitudes obtained in sinusoidal excitation for both cores were lower than the square wave excitation. The acceleration harmonic spectrum obtained under 50Hz operation was found to be much smoother than the acceleration harmonic spectrum at medium frequency, especially for 6,5% SiFe core.
Benzer Tezler
- AlxGa1-x As / GaAs Graded ındex separate confinement heterostructure single quantum well lasers
AlxGa1-x As / Ga As değişken kırılma indisli ayrık hapisli heteroyapı tek kuvantum kuyulu lazerler
MÜMTAZ KORAY BOZKURT
- Fe-B-Si metalik camlarının kristalizasyon kinetiğinin magnetik özellikler üzerindeki etkisi
Başlık çevirisi yok
ESRA ÖZKAN
- The preraration, characterization and sintering of nanocrystalline ceramics
Nanokristal seramik tozlarının üretimi, karakterizasyonu ve sinterlenmesi
ÖZLEM ÇAĞLAR
Yüksek Lisans
İngilizce
1999
İzmir Yüksek Teknoloji EnstitüsüMalzeme Bilimi ve Mühendisliği Ana Bilim Dalı
Yükleniyor...
- İyon implantasyonu yöntemiyle yüzeyi modifiye edilmiş 1.2080 soğuk iş takım çeliğinde implantasyon parametrelerinin mekanik ve tribolojik özellikler üzerine etkilerinin araştırılması
Studying the effects of implantation parameters at modified 1.2080 cold working tool steel on mechanical and tribological properties with ion implantation method
NURŞEN AKBAŞ
- Mekanik alaşımlanmış intermetalik toz ve sinter Ti-47-5Al-3Cr alaşımının analitik elektron mikroskop ve x-ışınları teknikleri ile karakterizasyonu
Analytical election microscope and x-ray diffraction characterization of mechanically alloyd intermetallic Ti-47-5Al-3Cr powder and sinter
ARDA GENÇ