Geri Dön

Yüksek gerilim izolatörlerinde yüzeysel atlamanın azaltılması için yeni bir yaklaşım

A new approach for reducing surface flashover in high voltage insulators

  1. Tez No: 637998
  2. Yazar: HARUN GÜLAN
  3. Danışmanlar: PROF. DR. MEHMET CEBECİ
  4. Tez Türü: Doktora
  5. Konular: Elektrik ve Elektronik Mühendisliği, Electrical and Electronics Engineering
  6. Anahtar Kelimeler: İzolatörlerde kirlenme atlaması, Kirlilik direnci, Atlama gerilimi, Yüksek darbe gerilimi, Su jeti, Pollution flashover in insulators, Pollution resistance, Flashover voltage, High impulse voltage, Water jet
  7. Yıl: 2020
  8. Dil: Türkçe
  9. Üniversite: Fırat Üniversitesi
  10. Enstitü: Fen Bilimleri Enstitüsü
  11. Ana Bilim Dalı: Elektrik-Elektronik Mühendisliği Ana Bilim Dalı
  12. Bilim Dalı: Elektrik Tesisleri Bilim Dalı
  13. Sayfa Sayısı: 152

Özet

Yüksek gerilim izolatörlerinde kirlenme nedeniyle oluşan yüzeysel atlama olayı enerjinin kesintiye uğramasına yol açabildiğinden sistemin enerji sürekliliği açısından olumsuz bir durum oluşturur. Atlama nedeniyle oluşabilecek olan bu durumu önleyebilmek için izolatörlere uygulanabilecek çeşitli tedbirler üzerine çok sayıda araştırma yapılmıştır. Yüzey kaçak akımlarının azaltılması amacıyla kaçak yolu direncinin artırılması, yani izolatör boyunun uzatılması, atlamaya karşı etkili bir tedbir olarak görülebilir. Ancak yüksek gerilimlerde izolatör boyundaki artış; direk boylarının, konsol açıklıklarının, sehim ve salınımların artmasına neden olacağından, bunların getireceği yeni sorunlar ve yüksek maliyet gibi olumsuzluklar söz konusudur. Bu çalışmada, yıldırım darbe gerilimlerini simüle eden bir sistem Matlab/Simulink paket programı yardımıyla oluşturulmuştur. Farklı darbe gerilimleri üreten bir yapı elde edilmiştir. İzolatör yapısı, bir su jeti sistemi ile modellenerek deneyler yapılmıştır. Su jeti deney sistemi, matematiksel bir model olmayıp bir mühendislik modelidir. Bir mühendislik modeli olduğundan tamamen sistem davranışının pratik hayattaki karşılığına odaklıdır. Su jeti sistemi farklı kirlenme derecelerine sahip olacak şekilde değiştirilmiştir. Bu aşamada suyun debisi sabit bırakılmıştır. Deneyler sırasında atlamayı azaltıcı etkisinin olacağı öngörülen indüktans eklenmiş yapılar kullanılmıştır. Kullanılan suyun sıcaklığının, tekrarlanan yıldırım darbe gerilimlerinin sayısına göre arttığı gözlenmiştir. İndüktans bağlı durumdaki deneyler sonucunda pozitif darbe gerilimlerinde atlama olayının negatif darbe gerilimindeki durumlara oranla daha düşük gerilim seviyelerinde olduğu tespit edilmiştir. İndüktans değerinin ve jet boyunun artmasının atlama gerilimini artırdığı belirlenmiştir. Yıldırım darbe gerilimleri uygulanan deneysel sistemin farklı indüktans değerine sahip yapılar sayesinde atlamayı azaltıcı, yani atlama gerilimini artırıcı etkisi gösterilmiştir.

Özet (Çeviri)

Since the surface flashover caused by contamination in high voltage insulators can cause energy interruption, it creates a negative situation in terms of the energy continuity of the system. In order to prevent this situation, which may occur due to flashover, a lot of research has been done on various measures that can be applied to the insulators. In order to reduce surface leakage currents for increasing the leakage resistance, that is extending the length of the insulator, can be seen as an effective measure against flashover. However, the increase in the length of the insulator in high voltages; there are new problems such as high costs, as it will cause the increase in post lengths, console openings, deflection and oscillations. In this study, a system that simulates lightning impulse voltages was created with the help of Matlab/Simulink package program. A structure producing different impulse voltages was obtained. Experiments were conducted by modeling the insulator structure with a water jet system. The water jet testing system is not a mathematical model but an engineering model. As it is an engineering model, it is completely focused on the response of system behavior in practical life. The water jet system has been changed to have different degree of contamination. At this stage, the flow of water was left constant. During the experiments, structures with added inductance, which are predicted to have a flashover-reducing effect, were used. It was observed that the temperature of the water used increased according to the number of repeated lightning impulse voltages. As a result of the experiments in inductance-connected state, it was determined that the flashover event was at lower voltage levels in positive impulse voltage compared to the situations in negative impulse voltage. It has been identified that the inductance value and the increase of the jet length increase the flashover tension. The experimental system with lightning impulse voltages has been shown to reduce the flashover, that is, the flashover voltage, thanks to structures with different inductance values.

Benzer Tezler

  1. Yüksek gerilim izolatörlerinde yüzeysel kaçak akımların anfıs ile hesaplanması

    Calculation of surface leakage current by anfis in high voltage insulator

    ERSİN TURAN

    Yüksek Lisans

    Türkçe

    Türkçe

    2018

    Elektrik ve Elektronik MühendisliğiFırat Üniversitesi

    Elektrik-Elektronik Mühendisliği Ana Bilim Dalı

    PROF. DR. MUHSİN TUNAY GENÇOĞLU

  2. Yüksek gerilim izolatörlerinde kirlenme atlamasının dinamik ark modeli

    Dynamic arc modeling of pollution flashover of high voltage insulators

    ZAFER AYDOĞMUŞ

    Doktora

    Türkçe

    Türkçe

    2000

    Elektrik ve Elektronik MühendisliğiFırat Üniversitesi

    Elektrik-Elektronik Mühendisliği Ana Bilim Dalı

    DOÇ.DR. MEHMET CEBECİ

  3. Kirlenmiş yüksek gerilim izolatörlerine seri bağlı endüktansın yıldırım darbe dayanımına etkisi

    Effect of inductance in series with polluted high voltage insulators on lightning impulse withstand

    YUNUS BALCI

    Yüksek Lisans

    Türkçe

    Türkçe

    2021

    Elektrik ve Elektronik MühendisliğiFırat Üniversitesi

    Elektrik-Elektronik Mühendisliği Ana Bilim Dalı

    PROF. DR. MEHMET CEBECİ

  4. Güç merkezi izolatörlerinde yüzey kaçak akımları için bir görüntü ve uyarı cihazının tasarımı

    Advancing of monitoring and alarm device for surface leakage currents an outdoor power plant insulators

    AHMET ŞENPINAR

    Yüksek Lisans

    Türkçe

    Türkçe

    1997

    Elektrik ve Elektronik MühendisliğiFırat Üniversitesi

    Elektrik-Elektronik Mühendisliği Ana Bilim Dalı

    DOÇ. DR. MEHMET CEBECİ

  5. Yüksek gerilim izolatörlerinin kirlenme atlama davranışlarının sonlu elemanlar yöntemi yardımıyla belirlenmesi

    Determination of pollution flashover behaviour of high voltage insulators by the finite element method

    MUHSİN TUNAY GENÇOĞLU

    Yüksek Lisans

    Türkçe

    Türkçe

    1997

    Elektrik ve Elektronik MühendisliğiFırat Üniversitesi

    Elektrik-Elektronik Mühendisliği Ana Bilim Dalı

    DOÇ.DR. MEHMET CEBECİ