Doğru akım uyartım altında güçtransformatörlerinin yeniden boyutlandırılması
Derating of power transformers under dc excitation
- Tez No: 788446
- Danışmanlar: PROF. DR. MURAT ERHAN BALCI
- Tez Türü: Doktora
- Konular: Elektrik ve Elektronik Mühendisliği, Electrical and Electronics Engineering
- Anahtar Kelimeler: Güç transformatörleri, azami yüklenme oranı, doğru akım uyartım, jeomanyetik olarak indüklenen akımlar, elektrik-manyetik eşdeğer devre modeli, relüktans tabanlı model. Bilim Kod / Kodları : 90513, 90514, 90515, Doğru akım, Güç transformatörü, Jeomanyetik alan, Relüktans motorları, Power transformers, maximum loading ratio, direct current excitation, geomagnetically induced currents, electric-magnetic equivalent circuit model, reluctancebased model, Direct current, Power transformer, Geomagnetic field, Reluctance motors
- Yıl: 2023
- Dil: Türkçe
- Üniversite: Balıkesir Üniversitesi
- Enstitü: Fen Bilimleri Enstitüsü
- Ana Bilim Dalı: Elektrik-Elektronik Mühendisliği Ana Bilim Dalı
- Bilim Dalı: Belirtilmemiş.
- Sayfa Sayısı: Belirtilmemiş.
Özet
Bu tez çalışmasında ilk olarak, doğru akım (DA) uyartım koşullarının tek fazlı kabuk tipi nüveli ve üç fazlı beş bacaklı çekirdek tipi nüveli güç transformatörleri üzerindeki etkilerini zaman verimli ve hassas bir şekilde analiz etmek için relüktans tabanlı modeller geliştirilmiştir. Geliştirilen modellerde literatürdeki diğer relüktans tabanlı transformatör modellerinden farklı olarak sargı kayıplarının frekansa bağımlılığı dikkate alınmıştır. İkinci olarak, sonlu elemanlar yöntemi analizi ile elde edilen sonuçlar referans alınarak, geliştirilen modellerin geçerlilikleri saf sinüzoidal ve DA bileşenli gerilim durumları için doğrulanmıştır. Daha sonra, DA uyartımın dikkate alınan transformatör tipleri üzerindeki etkileri geliştirilen modeller kullanılarak analiz edilmiştir. Bu analizlerden, DA uyartımın transformatörlerde doymaya yol açabileceği ve bu doymaya bağlı olarak transformatör kayıplarının, reaktif güç talebinin ve uyartım akımı harmonik bozulmasının önemli derece artacağı görülmüştür. Bununla birlikte, DA uyartım altında transformatörlerin yeniden boyutlandırılması için anma primer akım etkin değeri, anma toplam kaybı ve anma primer sargı kaybı sınırlamalarına dayanan üç farklı azami yüklenme oranı (AYO) belirleme yöntemi karşılaştırmalı olarak analiz edilmiştir. Bu analizden, anma primer sargı kaybı tabanlı yaklaşımın, DA uyartım koşulları altında transformatörlerin aşırı ısınmadan çalışması için diğer iki yaklaşıma kıyasla daha güvenilir olduğu sonucuna varılmıştır. Son olarak, manyetik nüve malzemesi cinsi ve nüve kesit alanı boyutlandırma, tasarım seçeneklerinin DA uyartım altında AYO iyileştirmesine etkileri analiz edilmiştir.
Özet (Çeviri)
In this thesis, firstly, to time efficiently and sensitively analyze the direct current (DC) excitation conditions' effects on single-phase shell type and three-phase five-leg core type power transformers, their reluctance-based models are developed. In the developed models, unlike other reluctance-based transformer models in the literature, the frequency-dependent nature of the winding losses has been taken into consideration. Secondly, for pure sinusoidal and DC biased voltage cases, the validity of the developed models has been verified by using the results of the finite element method as a reference. Then, the effects of DC excitation on the considered transformer types are analyzed with using the developed models. It is seen from the analysis results that DC excitation can cause saturation in transformers, and depending on the saturation, their losses, reactive power demand, and harmonic distortion of the excitation current can increase significantly. In addition, three different maximum loading ratio (MLR) determination methods, which are based on the rated primary current effective value, rated total loss, and rated primary winding loss limitations, are comparatively analyzed for the derating of transformers under the DC excitation conditions. From the analysis, it is concluded that the rated primary winding loss-based approach is more reliable than the other two approaches for transformers to operate without overheating under DC excitation conditions. Finally, under DC excitation, the effects of design choices such as magnetic core material type and core cross-sectional area sizing on the improvement of the MLR are analyzed.
Benzer Tezler
- Landsat uydusu aracılığı ile elde edilen görüntülerin sınıflandırılmaları ve bunlara ilişkin bilgisayar programlarının hazırlanması
Başlık çevirisi yok
G. FERZAN KÜÇÜKA
Yüksek Lisans
Türkçe
1985
Ege ÜniversitesiBilgisayar Bilimleri ve Mühendisliği Ana Bilim Dalı
Yükleniyor...
- Dokuma kumaşlarda örgü tipinin ham kumaşın boyutları ve geometrik özellikleri üzerindeki etkilerinin araştırılması
Başlık çevirisi yok
EMEL ÖNDER
- Realization of transmitter and receiver clock generation units and channel switching unit in a modified analog radio relay
Değiştirilen bir analog radyodaki verici ve alıcı saat üretimi birimleri ve kanal anahtarlama biriminin gerçekleştirilmesi
AYHAN BÜYÜKSEMERCİ
Yüksek Lisans
İngilizce
1987
Orta Doğu Teknik ÜniversitesiElektrik-Elektronik Mühendisliği Ana Bilim Dalı
Yükleniyor...
- The Effect of government price support on wheat farming and wheat marketing in Turkey
Başlık çevirisi yok
GÜNEŞ GÜLSEN ÖZEL
Yüksek Lisans
İngilizce
1987
Orta Doğu Teknik ÜniversitesiYöneylem Araştırması Ana Bilim Dalı
Yükleniyor...
- New algorithms and techniques for microprocessor-controlled PWM induction drives
Başlık çevirisi yok
OSMAN KÜKRER
Doktora
İngilizce
1987
Orta Doğu Teknik ÜniversitesiElektrik-Elektronik Mühendisliği Ana Bilim Dalı
Yükleniyor...